PERFORMANCE DATA
ASHRAE Standard 52.1-1992
Model Number: 1172 BWL
Dimension: 24" x 24" x 2"
Initial Resistance at 300 FPM: 0.08" W.G.
Final Resistance: 0.75" W.G.
Initial Atmospheric Dust Stop Efficiency:
<20%
Average Atmospheric Dust Stop Efficiency:
<20%
Average Synthetic Dust Weight Arrestance: 80% |