| Air filters shall be Farr E-Series RIGA-FLO (65) (85) (95)
high performance, deep-pleated, totally rigid and disposable type,
constructed completely without steel components. Manufacturer shall
provide MSDS sheets upon request demonstrating that the only by-products
of the grille's combustion are carbon dioxide and water. Filter
components shall emit no phenols during incineration.
Each filter shall consist of FARR FLO high efficiency media, Dura-Ply
enclosing frame, contour stabilizers on both air entering and air
exiting sides and support grilles. Filters shall be classified by
Underwriter's Laboratories as Class 2 and shall be capable of
withstanding 10" w.g. pressure drop with minimal change to media
pack sealing integrity.
E-Series RIGA-FLO 65 - Filter media shall be FARR-FLO high
loft glass fiber type with integral backing that will maintain
structural stability of the pack without the use of expanded metal,
metal wires or grids. Filter shall have an average efficiency of 60-65%
on ASHRAE Test Standard 52.1-92 an average arrestance of not less than
97.5% on that standard, and a minimum efficiency of 12.0% on 0.3 micron
atmospheric dust. Initial resistance at 500 fpm approach velocity shall
not exceed .31" w.g.
E-Series RIGA-FLO 85 - Filter media shall be FARR-FLO high
loft glass fiber type with integral backing that will maintain
structural stability of the pack without the use of expanded metal,
metal wires or grids. Filter shall have an average efficiency of 80-85%
on ASHRAE Test Standard 52.1-92 an average arrestance of not less than
99.0% on that standard, and a minimum efficiency of 48.0% on 0.3 micron
atmospheric dust. Initial resistance at 500 fpm approach velocity shall
not exceed .50" w.g.
E-Series RIGA-FLO 95 - Filter media shall be FARR-FLO high
loft glass fiber type with integral backing that will maintain
structural stability of the pack without the use of expanded metal,
metal wires or grids. Filter shall have an average efficiency of 90-95%
on ASHRAE Test Standard 52.1-92 an average arrestance of not less than
99.5% on that standard, and a minimum efficiency of 60.0% on 0.3 micron
atmospheric dust. Initial resistance at 500 fpm approach velocity shall
not exceed .57" w.g.
ENCLOSING FRAME - Enclosing frame shall be Farr Dura-Ply,
constructed by bonding a moisture and corrosion resistant laminate
between layers of film with the use of a waterproof adhesive. The media
pack shall be both mechanically and chemically bonded to the Dura-Ply
frame on all sides to eliminate the possibility of air bypass. The Dura-Ply
frame shall be equipped with a high impact, non-metallic grille
installed on both air entering and air exiting sides and mechanically
fastened to the frame and to each contour stabilizer. |
CONTOUR STABILIZERS - Contour
stabilizers shall be of PMDI (polymeric methylene diisocyanate)
impregnated board for enhanced waterproofing and shall be permanently
installed on both the air entering and air exiting sides of the filter
media pack to help maintain pleat stability. There shall be four contour
stabilizers each on the air entering and air exiting sides.
TYPE 8 HOLDING FRAMES (Built-up Filter banks) - Holding frames
shall be factory fabricated of 16-gauge galvanized steel and shall be
equipped with gaskets and four heavy duty Farr C-80 positive sealing
fasteners. Each fastener shall be capable of withstanding 25 lb.
pressure without deflection. They shall be capable of being attached or
removed without the use of tools.
GLIDE/PACKS (Side Access Applications) - Filter housings shall
be Farr Model 3P universal Glide/Pack or ECO Glide/Pack. They shall be
factory fabricated and assembled. The units shall be constructed of not
less than 16-gauge galvanized steel. They shall incorporate two (2)
access doors, extruded aluminum tracks and individual Universal Holding
Frames designed to accommodate a wide range of standard size filters is
varying efficiency ranges.
PREFILTERS - Prefilters shall be 2" or 4" Farr
30/30s, medium efficiency, pleated disposable type. Each filter shall
consist of a non-woven cotton fabric media, media support grid and
enclosing frame. Prefilters shall be capable of being installed or
removed, using the Farr C-102 E-Series fastener, without disturbing the
seal on the E-Series RIGA-FLO filter.
FARR OFFERS RIGID AIR FILTERS FOR EVERY NEED...
RIGA-FLO - For years the industry standard in rigid
filtration, the Farr RIGA-FLO comes in four efficiencies, a wide
range of sizes. 12" and 6" depths, U.L Class 2 or 1, and with
or without headers, for versatile performance.
P-Series RIGA-FLO - Uses an economical synthetic media with
outstanding pressure drop performance, U.L. Class 2, 12" depth,
65%, 85%, and 95% efficiencies.
RIGA-RP AIR FILTRATION SYSTEM - Unique design combines a
permanent all-metal filter frame with lightweight, replaceable
filtration panels. Panels available in 65%, 85%, and 95% efficiencies
and Farr-Sorb PS Carbon for high efficiency odor and VOC control, U.L.
Class 2. |