| AIR FILTERS - Air filters shall be Farr
Aeropleat III, medium efficiency, pleated, disposable type. Each
filter shall consist of a non-woven cotton and synthetic fabric
media support grid and enclosing frame. The filter shall be listed
by Underwriter's Laboratories as Class 2.
FILTER MEDIA - Filter media shall be non-woven cotton
fabric type. The filter media shall have an average efficiency of
25-30% on ASHRAE Test Standard 52.1-92.
1 INCH - Filter face shall contain not less than 12
pleats per linear foot. Initial resistance at 500 fpm shall not
exceed 0.22" w.g.
2 INCH - Filter face shall contain not less than 10
pleats per linear foot. Initial resistance at 500 fpm shall not
exceed 0.23" w.g.
4 INCH - Filter face shall contain not less than 9
pleats per linear foot. Initial resistance at 500 fpm shall not
exceed 0.19" w.g. |
MEDIA SUPPORT GRID - The media
support grid shall be a welded wire grid with an effective open
area of not less than 96%. The welded wire grid shall be bonded to
the filter media to eliminate the possibility of media
oscillation, media pull away, and air bypass.
The media support grid shall be formed in such a manner that it
effects a radial pleat design, allowing total use of filter media.
ENCLOSING FRAME - The enclosing frame shall be
constructed of a rigid, heavy-duty board, with diagonal support
members bonded to the air entering side of each pleat, to ensure
pleat stability. The inside periphery of the enclosing frame shall
be bonded to the filter pack, thus eliminating the possibility of
air bypass.
*The Farr Aeropleat III is categorized as a
30% efficiency filter. Average efficiencies may vary 5 points.
These variances are typical of filters in the medium efficiency
category when tested in accordance with the ASHRAE 52.1-92
standard. |